MEMO
MEMO TO: GENERAL PUBLIC/BUILDING CONTRACTOR
MEMO FROM:
PLANNING DEPARTMENT
MEMO RE: MINIMUM ACCEPTABLE PRACTICES FOR ONE
AND TWO
FAMILY CONSTRUCTION
DATE:
DECEMBER 7, 1999
Listed
below are the minimum acceptable practices for 1-2 family construction .
These
practices are effective immediately:
1.
FOOTINGS: Thickness 8" Width 16"
2.
FOUNDATION WALLS: Single Story: 8"
thick exterior damp proofing required.
Two Story and Above: 10"
3.
FOUNDATION DRAINAGE:
·
Perimeter
drains are required
·
Perforated
drainage pipe should be installed at or below area being protected and should
discharge by gravity or mechanical means.
4.
LALLY COLUMNS PADS: Thickness 8" Dimension 24" x 24"
5.
SILLS:
·
Double
2" x 6"
·
Bottom
plate to be pressure treated and equipped with sill insulation
·
1/2"
x 8" anchor bolts 6'O.C. (straps are not allowed)
6.
BEAM POCKET: Size of beam pocket should
not be greater than three inches in
height/width of beam being used.
7. MAXIMUM CLEAR SPAN OF 1ST
FLOOR, FLOOR JOIST
16"
O.C. 12" O.C.
2x8 11' 8" 12' 10"
2x10 14' 11" 16' 5"
2X12 18' 1" 19' 11"
8.
MAXIMUM CLEAR SPAN OF 2ND
FLOOR, FLOOR JOIST
16" O.C. 12"
O.C.
2X8 12'
10" 14' 2"
2X10 16'
5" 18' 0"
2X12 19' 11" 21' 11"
9.
BRIDGING: 1X3 wood or metal required on either side of carrying beam
10.
SUB FLOOR: 3/4" t.g. plywood or O.S.B. glued and nailed (Particle board
is not allowed for 1st and 2nd
floor sub flooring.
11.
EXTERIOR WALLS
·
2"
X 6" 16' O.C.
·
1/2"
plywood or O.S.B. sheeting
·
Tyvek
or equal required
12. ROOFS
·
1/2"
plywood or O.S.B. sheeting
·
Roofs
with 6" pitch or less require one course of ice/water shield at roof edges
·
Roofs
with 6" pitch or greater require one course of 15 lb. Felt at roof edges
·
Proper
venting required
13. DECKS:
·
Decks
to be made of P.T. material or equal, such as douglas fir, etc.
·
Decks
must be lag bolted 32" O.C. top and bottom
·
Joist
hangers or approved equal method must be used
·
Support
post must be lag bolted or notched a minimum of 1/2" into deck framing
·
Flashing
must be installed where deck is attached to house in such a way that it will
prevent water from seeping in between deck and house
·
Post
must sit on galvanized post bracket fastened on or poured into concrete support
pier
·
Bury
of wood post is not permitted
·
Rail
eight minimum of 40"
·
Ballister
spacing - maximum 4" between ballisters
14.
PRECAST STAIRS: Exterior precast concrete
stairs must rest on a concrete pad, a minimum of 4" thickness, and no smaller than the
base of the stairs.